6.1.2 Synchronizing the Configuration Parameters

Procedure
Step 1 After replacing components, log in to the ECC800-Pro WebUI and choose Maintenance >
Parameter Sync to access the parameter synchronization page.
Step 2 Click Device type and select the component type from the drop-down list.
Step 3 Select the failure device in Source Device, select the reserved device in Target Device, and
click Submit to synchronize the configuration parameters of the failure device to the reserved
device.
----End
Issue 04 (2020-03-25)
Figure 6-4 WebUI login page
On the login page, enter the preset user name admin and preset password Changeme,
set the language, and click Log In.
After the first login, change the password in time to ensure account security and prevent
unauthorized network attacks, such as data tampering. Huawei will not be liable for any security
issues caused by your failure to change the preset password in time or password loss after changing.
Change the password of the user account periodically.
Record and keep the password properly. If you forgot the password, you will be unable to log in to
the WebUI.
When the event notification is configured and the password retrieval mode is configured under user
management, the password can be retrieved.
An account is logged out due to timeout if no operation is performed within 10 minutes after system
login.
A maximum of three users can log in to the ECC800-Pro WebUI at the same time.