SmartDC
Maintenance Guide
Table 4-10 Semiannual maintenance for the management system
Item
Check the availability of
the smart ETH gateway.
Check the availability of
the rack environment
unit.
Check the availability of
the UIM20A expansion
module.
Check the availability of
the AC actuator.
Issue 04 (2020-03-25)
Operation
On the WebUI of the
ECC800, choose
Monitoring > System >
Smart ETH Gateway
Group > Smart ETH
Gateway to enter the
operating information
page, and check the
communications, PoE
port connection, and
power supply.
On the WebUI of the
ECC800, choose
Monitoring > IT
Cabinet > Rack
Environment Unit to
enter the operating
information page, and
check the communication
status and temperature.
On the ECC800-Pro
WebUI, choose
Monitoring > Cabinet >
UIM Group > UIM 1 to
enter the operating
information page, and
check information such as
communication status and
temperature.
1. On the ECC800
WebUI, choose
Monitoring > Aisle >
AC Actuator
Group > AC
Actuator > Running
Parameters, set Set
light mode to
Manual, and click
Submit.
2. On the WebUI of the
ECC800, choose
Monitoring > Aisle >
AC Actuator
Group > AC
Actuator to enter the
Controls page, and
remotely control the
lights.
NOTE
Copyright © Huawei Technologies Co., Ltd.
Standard
On the WebUI of the
ECC800, check that the
PoE port connection and
power supply in the smart
ETH gateway is normal.
The communication,
temperature, and door
status information of the
rack environment unit are
normally displayed on
the WebUI of the
ECC800.
The communication and
temperature information
of the UIM20A
expansion module are
normally displayed on
the ECC800-Pro WebUI.
Lights in the smart
module aisle can be
normally controlled
through the AC actuator.
4 Routine Maintenance
Troubleshooting
If the PoE port
connection and power
supply in the smart ETH
gateway is not normal,
check whether the
communications cable is
loose or disconnected. If
so, reconnect the cable. If
not, replace the smart
ETH gateway.
If the display is not
normal, check whether
the communications
cable is loose or
disconnected. If so,
reconnect the cable. If
not, replace the rack
environment unit.
If the display is not
normal, check whether
the communications
cable is loose or
disconnected. If so,
reconnect the cable. If
not, replace the UIM20A
expansion module.
If the lights cannot be
normally controlled,
check whether the AC
power cable to the lights
is loose or disconnected.
If so, reconnect the cable.
If not, replace the AC
actuator.
29