7.2 Specifications
Item
Number of Channels
Supported Redundancy
Shared IONet
Required ControlST and YUAA
Versions
Auto-Reconfiguration
RJ-45 Ethernet Ports
Fastest Frame Rate Supported
Supported I/O Types
Incoming Control Power
Incoming Power Consumption
Power Output to Field Device
I/O Pack Internal Current Limiter
I/O Pack Hot Swap Replacement
28 V dc Power Connector
Rating for Ambient Temperature on
Module Exterior During Operation
Storage Temperature Rating
Relative Humidity Required
Lightning Strike Protection
Operating Vibration
Flammability Rating
I/O Pack Casing Protection Against
Intrusion
General I/O Pack Specifications
YUAA Module Dimensions
Mode Miswired Tolerance
172
GEH-6855_Vol_II

YUAA Specifications

Specification
16 channels, with groups of three terminals per channel
Simplex
Supported
ControlST Software Suite V07.02.00C or later
YUAA firmware V05.05.00 or later
Supported
Supports dual Ethernet (IONet) networks
10 ms
Thermocouple
RTD
4–20 mA current input with HART option
± 5 V or ± 10 V input
0–20 mA current output with HART option
Digital inputs and outputs
Pulse accumulators
28 V dc source is required
Power consumption is based on 8.1 watts quiescent plus power per channel modes as follows:
• TC, 5V, 10V, externally wetted discrete inputs, pulse accumulator inputs, or RTD modes = 0.02 watts
per channel
• External fed mA input and internally wetted discrete inputs = 0.04 watts per channel
• Internal fed mA input or mA output = 0.68 watts per channel or less, depending on external loop
resistance
From SUAA screws PWR_RTN, supply is a maximum 2 V less than the incoming control power to the
YUAA I/O pack
2.5 A to limit impact to supply if a short circuit failure should occur
Supported
Phoenix
®
contact part number MC 1.5/S-STF-3.81
-40 to 70°C (-40 to 158 °F)
-40 to 85°C (-40 to 185 °F)
5 to 95% non-condensing
UL61010-1
IEC/EN 60068-2-6
UL94V-2
Ingress Protection Code: IP20 per EN 60529
Refer to GEH-6855_Vol_I for technical regulations and standards that apply to all of the Mark VIeS
Functional Safety System equipment
6.6 in L x 3.4 in W x 4.3 in H (with I/O pack attached)
Average panel area/channel is equal to small S card footprint per group of 16 channels
Refer to the ToolboxST Configuration
when incorrectly wired or configured.
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Modes
section for details regarding YUAA resistance to damage
Public Information