Jpdf Dc 125V Ground Magnitude (Jd1/Jz2/Jz3 Connector) Out Of Range; Jpdf Fuse Fu1R Or Fu2R (J1R Connector) Is Blown Or Sw1R Switched Off - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

113, 115
Description JPDF-[ ] DC 125V Ground magnitude (JD1/JZ2/JZ3 connector) out of range
Possible Cause
The 125 V ground feedback magnitude is greater than Gnd_Mag_Trig_Volt.
Gnd_Mag_Trig_Volt is set too low.
One side of the dc 125 V source voltage is grounded.
Solution
Verify that Gnd_Mag_Trig_Volt is set correctly.
Check the connections to the specified connector.
Verify the grounding of the dc input signals. Refer to the JPDF help documentation.
If DC 125V input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
116, 125
Description JPDF-[ ] fuse FU1R or FU2R (J1R connector) is blown or SW1R switched OFF
Possible Cause
The SW1R is turned off and FuseDiag is enabled.
The FU1R or FU2R fuse is blown.
The 125V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
PDM Power Distribution Modules
Public Information
GEH-6855_Vol_II System Guide 333

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents