GE Mark VIeS System Manual page 335

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

119, 128
Description JPDF-[ ] fuse FU71 or FU72 (J7X connector) is blown or SW7X switched OFF
Possible Cause
The SW7X is turned off and FuseDiag is enabled.
The FU71 or FU72 fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
120, 129
Description JPDF-[ ] fuse FU73 or FU74 (J7Y connector) is blown or SW7Y switched OFF
Possible Cause
The SW7Y is turned off and FuseDiag is enabled.
The FU73 or FU74 fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
PDM Power Distribution Modules
Public Information
GEH-6855_Vol_II System Guide 335