Description JPDF-[ ] fuse FU71 or FU72 (J7X connector) is blown or SW7X switched OFF
Possible Cause
•
The SW7X is turned off and FuseDiag is enabled.
•
The FU71 or FU72 fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
120, 129
Description JPDF-[ ] fuse FU73 or FU74 (J7Y connector) is blown or SW7Y switched OFF
Possible Cause
•
The SW7Y is turned off and FuseDiag is enabled.
•
The FU73 or FU74 fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.