Jpdc-Fuse Fu1R Or Fu2R (J1R Connector) Is Blown Or Sw1R Switched Off; Jpdc-Fuse Fu1S Or Fu2S (J1S Connector) Is Blown Or Sw1S Switched Off - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

177
Description JPDC-Fuse FU1R or FU2R (J1R connector) is blown or SW1R switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
178
Description JPDC-Fuse FU1S or FU2S (J1S connector) is blown or SW1S switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
348
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II