Yuaa Orderable Part Numbers - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

Channel
Rating
Configuration
Discrete Outputs
Up to 24 mA at up to 22 V using mA output mode, capable of driving control circuits of many external interposing
electromagnetic (Phoenix Contact 2961105 on DIN base PLC-BSP-24DC/21) or solid state (Crydom DC60S7 60 V
dc 7A) relays using under 22 mA control current with panel or DIN-rail mounting near the SUAA base.
SOE is not supported on analog outputs to drive external interposing circuits.
Pulse Accumulators
16-bit accumulator
Voltage range: -10 to 20 V
Frequency range: 0 to 500 Hz
Part Numbers
Description
IS430SSUAH1A
Complete assembled Simplex module made up of one IS420YUAAS1A attached to one IS410SUAAS1A, and
includes the base/mounting and hardware/cover
IS420YUAAS1A
YUAA I/O module with captive mounting screws
IS410SUAAS1A
Simplex terminal board on DIN-rail mountable base
IS400SUAAS1A
Simplex terminal board only
Note For more information, refer to the Mark VIeS Functional Safety Vibration Input Module Summary Sheet (GEI-100865).
YUAA Universal I/O Modules
YUAA Performance (continued)

YUAA Orderable Part Numbers

Public Information
GEH-6855_Vol_II System Guide 175