Communication Lost On Hssl Link 1; Communication Lost On Hssl Link 2; Communication Lost On Hssl Link 3; Configuration Mismatch With Auto-Reconfiguration Server - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

451
Description

Communication Lost on HSSL Link 1

Possible Cause
The UCSA can no longer communicate with the acquisition card on High Speed Serial Link 1
Solution
Verify that the Ethernet cable is connected and that the acquisition card is healthy.
452
Description

Communication Lost on HSSL Link 2

Possible Cause
The UCSA can no longer communicate with the acquisition card on High Speed Serial Link 2
Solution
Verify that the Ethernet cable is connected and that the acquisition card is healthy.
453
Description

Communication Lost on HSSL Link 3

Possible Cause
The UCSA can no longer communicate with the acquisition card on High Speed Serial Link 3
Solution
Verify that the Ethernet cable is connected and that the acquisition card is healthy.
485
Description

Configuration mismatch with Auto-Reconfiguration server

Possible Cause
Some or all of the I/O pack or module configuration files do not match those on the
Auto-Reconfiguration server
Solution
Perform a scan and download using the ToolboxST application
490
Description Software watchdog has been disabled
Possible Cause
A runtime malfunction has disabled the software watchdog protective function.
An invalid version of firmware has been downloaded.
Solution
Reload the base load, firmware, and application code to the I/O pack or module, and restart.
If failure persists, remove the flash memory from the controller and reprogram the boot loader using the ToolboxST
application. Download using the Device | Download | Controller setup | Format Flash selection. After reinstalling the
flash memory and restarting, reload the firmware and application code.
If the problem persists, replace the I/O pack or module or the controller.
472
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information