Outputs - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

4.1.6.3 Outputs

Output Name
Output Description
AnalogOutput01 -
First of two analog outputs - board point, Point edit
AnalogOutput02
Output_MA
Output current, mA selection.
OutputState
State of the outputs when offline. When the YAIC loses
communication with the controller, this parameter determines
how it drives the outputs:
PwrDownMode - Open the output relay and drive outputs to
zero current
HoldLastVal - Hold the last value received from the controller
Output_Value - Go to the configured output value set by the
parameter Output_Value
Output_Value
Pre-determined value for the outputs
Low_MA
Output mA at low value
Low_Value
Output in Engineering Units at Low_MA
High_MA
Output mA at high value
High_Value
Output value in Engineering Units at High_MA
TMR_Suicide
Enables suicide for faulty output current, TMR only
TMR_SuicLimit
Suicide threshold (Load sharing margin) for TMR operation, in
mA
D/A_ErrLimit
Difference between D/A reference and feedback, in % for
suicide, TMR only
Dither_Ampl
Dither % current of Scaled Output mA
Dither_Freq
Dither rate in Hertz
YAIC Analog I/O Modules
Public Information
Choices
Output REAL
Unused, 0-20 mA
PwrDownMode
HoldLastVal
Output_Value
-3.4082 e + 038 to 3.4028 e + 038
0 to 200 mA
-3.4082 e + 038 to 3.4028 e + 038
0 to 200 mA
-3.4082 e + 038 to 3.4028 e + 038
Enable, Disable
0 to 200 mA
0 to 200 %
0 to 10
Unused, 12.5hz, 25hz, 33.33hz, 50hz, 100hz
GEH-6855_Vol_II System Guide 99