Trlys1D Compatibility; Trlys1D Installation; Trlys1D Terminal Board Wiring - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

6.6.1 TRLYS1D Compatibility

Connector JA1 is used for a simplex I/O pack, and connectors JR1, JS1, and JT1 are used for TMR I/O packs.
Board Revision
Mark VIeS IS420YDOAS1B
TRLYS1D
Yes, all versions

6.6.2 TRLYS1D Installation

Connect the wires for the six relay outputs directly to the TB1 terminal block on the terminal board. The block is held down
with two screws and has 24 terminals accepting up to #12 AWG wires. A shield terminal strip, attached to chassis ground, is
located immediately to the left of the terminal block.
Connect the solenoid power for outputs 1-6 to JF1. JF2 can be used to daisy-chain power to other TRLYs. Do not use TB3.
YDOA Discrete Output Modules
Safety Rated
IEC 61508 safety certified with Mark VIeS YDOA

TRLYS1D Terminal Board Wiring

Public Information
GEH-6855_Vol_II System Guide 151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents