Ucsc Restore; To Perform Ucsc Restore - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

2.1.11 UCSC Restore

After installing a replacement controller, perform the following procedure to apply the configuration to the UCSC controller
and allow communication between the UCSC and the ToolboxST application. The Physical Presence (PHY PRES) button
located on the front of the controller is used to initiate the procedure.
Note The UCSC, as shipped from the factory, does not include the software on the controller to support communication
from the PHY PRES button to the EFA. The user needs to download to the controller at least once (using ToolboxST) to
enable this.
➢ ➢ To perform UCSC restore
From the ToolboxST Component Editor Device menu, select Download, then select Controller Setup.
1.
When the Controller Setup Wizard Welcome window displays, click Next.
2.
Select Initialize USB Flash Device, then click Next.
3.
4.
Insert a non-encrypted USB 2.0 (only) flash device with a 4 GB minimum capacity into the HMI computer USB port.
Click Scan and select the listed flash drive.
5.
Select the correct Channel (R, S, or T if using redundant controllers).
6.
Click Write, then click Next.
7.
8.
Complete the controller restore process using the instructions provided on the Controller Setup Wizard window or using
the remaining steps in this procedure.
9.
Remove the USB flash device from the HMI computer.
10. Remove power from the controller.
11. Insert the USB flash device into either USB port of the controller.
12. Press and hold in the PHY PRES button, and apply power to the controller. Continue to hold in the PHY PRES button
until the USB On LED is lit (~ 15 seconds).
13. Release the PHY PRES button and wait for the process to complete. (The USB On LED remains lit to indicate the restore
is in progress. The procedure takes one to two minutes.) When the LED turns off, the restore has completed successfully.
Note If the LED flashes at a 1 Hz rate, a failure has occurred. Retry or remove the USB flash device.
14. Remove the USB flash device from the controller.
15. Cycle power on the controller.
16. From the ToolboxST Controller Setup Wizard window, click Finish.
17. Perform a Download to bring the controller back online and in the controlling state.
36
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents