Description Startup sequence failed - Data initialization timeout T processor
Possible Cause Controller is unable to complete startup data initialization.
IONet malfunction
Controllers have different application revisions
One or more controllers are powered down
Controller is overloaded by external command messages
Solution
Check for disconnected IONet cables or malfunctioning network switches.
Rebuild and download application.
Ensure all controllers are powered up.
Disable all other command senders (for example, Modbus masters) until controller is online.
332
Description Overtemperature - Controller rebooted and throttled
Possible Cause
Excessive ambient temperature
Hardware malfunction
Fan loss
Solution
Check ambient temperature.
Check for dust buildup on the cabinet filters, controller, and power supply.
Replace the controller.
Check fans.
334
Description Application Error – [ ] Frame Skips Detected
Possible Cause
Hardware or IONet malfunction
Frame number skips detected. Frame number should monotonically increase until rollover; alarm occurs following a
single frame number skips in successive frames.
Solution
Check IONet (switches, cables).
Replace the controller.