Configuration Load Failure; Pack Firmware Error - Inputs Are Not Being Updated; Outputs Are Not Being Received - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

301
Description

Configuration Load Failure

Possible Cause
I/O pack or module I/O configuration files missing
I/O pack or module reseated on the terminal board (clears configuration from I/O pack or module)
Solution
Rebuild and download the application to all the processors.
Reload the firmware and application.
If the problem persists, replace processor module.
338
Description

Pack Firmware Error - Inputs are not being updated

Possible Cause
During commissioning or maintenance:
The I/O pack or module application process is not providing system signal inputs to EGD every frame.
Solution
During commissioning or maintenance:
Rebuild and download the firmware and the application.
Verify that the idle time is adequate for the I/O pack or module and that the frame rate does not exceed defined limits.
If the problem persists, replace the I/O pack or module.
339
Description

Outputs are not being received

Possible Cause
I/O pack or module not receiving outputs from the controller after previously receiving outputs
Controller is restarting or has restarted
Failed Ethernet connection between the I/O pack or module and controller
Internal firmware failure
Solution
Check for disconnected IONet cables or malfunctioning network switches.
Verify that the controller is online and operating correctly.
Rebuild and download the firmware and configuration to the I/O pack or module.
Common I/O Module Functionality
Public Information
GEH-6855_Vol_II System Guide 463