2402
Description EtherCAT linebreak detected between devices [ ] and [ ]
Possible Cause
An Ethernet cable is disconnected or damaged
EtherCAT device(s) is unplugged or without power
Solution
Reconnect Ethernet cables.
Verify all Ethernet LINK lights are lit.
Verify all EtherCAT devices are powered.
2404
Description EtherCAT limit for lost frames has been exceeded
Possible Cause
A device or network component is corrupting the EtherCAT frame
An Ethernet cable is damaged
Solution
Use Controller Advanced Diagnostic tool to determine where network issues are located in the device topology.
2405
Description EtherCAT device disconnected
Possible Cause
EtherCAT device(s) is unplugged or without power
An Ethernet cable is disconnected or damaged
Solution
Ensure all devices are connected and powered.
Verify all Ethernet LINK lights are lit.
2406
Description EtherCAT device in unexpected state
Possible Cause EtherCAT device(s) have invalid configuration or have experienced a watchdog event.
Solution Check the EtherCAT device configuration in the ENI file and EtherCAT Configuration Tool.
2407
Description EtherCAT Master in unexpected state
Possible Cause Bus does not match ENI file.
Solution Download a new ENI file or plug in all devices.