1.3 Specifications

Item
PROFINET support
RX3i Controller version
required
RXi Controller version
required
Proficy Machine Edition
version required
Power requirements
Module dimensions
Operating temperature
range
Number of port
connectors
USB connector (for
firmware upgrades)
PNS Status and Control
bits
I/O data update on the
PROFINET LAN
Number of IP
addresses
Number of MAC
addresses
I/O station maximum
limits
Configuration
Note:
For product standards, general operating specifications, and installation requirements,
refer to PACSystems RX3i System Manual, GFK-2314.
Value does not include the power consumption of the installed I/O modules. When calculating the total power
2
requirements, you will need to add the power consumption of the I/O modules according to the I/O module datasheet.
GFK-2883E
Specification
PROFINET Version 2.3 Class A I/O-Device
IC695CPU315/CPU320/ CPE305/CPE310/CPE330/CRU320 with firmware version
8.50 or later. All versions of CPE302.
IC69PNC001 PROFINET I/O-controller with firmware version 2.20 or later
RXi Controller with firmware version 7.80 or later is compatible with CEP001 up to
version 2.01, but is not compatible with CEP001 version 2.30 or later.
Version 8.6 with SIM3 or later
IC695CEP001: 5.25W (0.22 A) at 24 Vdc with or without Expansion Carrier
(IC694CEE001)1
2
DC power supply input range: 19.2V – 30V
177.2 mm x 51 mm x 35 mm (6.98 in x 2.01 in x 1.38 in)
Same for CEP001 and CEE001.
0°C to 60°C (32° F to 140° F) maximum surrounding air temperature
IC695CEP001: Two RJ-45 10/100BASE-TX receptacles
IC694CEE001: None
IC695CEP001: One Micro-B connector. USB 2.0 compliant running at Full-speed
(12 MHz) in device mode
IC694CEE001: None
32 input status bits and 32 output control bits
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms
One. Supports Classless Inter-Domain Routing (CIDR)
Three. One per external port and one internal. External MAC addresses are only
used for specialized Ethernet protocols such as MRP or LLDP
Number of I/O Modules per station
I/O data per station
V2.3 GSDML file is included with Proficy Machine Edition; available for import into
3rd-party tools
March 2018
Chapter 1. Overview
IC695CEP001: One
IC695CEP001 with IC694CEE001: Two
1024 bytes total
512 bytes of input data
512 bytes of output data
3