Controller Password Protection; Shared Ionet; Black Channel Safety Communication; Controller Setup And Download - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

2.2 Controller Password Protection

Beginning with controller firmware V06.00.00C, password protection can be applied as a security measure to restrict access
to the controller. The password has an eight-character limit and other requirements. For the instructions to set password
protection, change the password, and other details, refer to the ToolboxST User Guide for Mark VIeS Functional Safety
Systems (GEH-6862), the section System Password Protection for the component.

2.3 Shared IONet

The Shared IONet function (with ControlST V04.06 or higher) enables the sharing of Mark VIeS Safety inputs with another
basic process Mark VIe controller set, saving the cost of redundant sensors and I/O. Refer to the Mark Controllers Shared
IONet User Guide (GEH-6812) for more information.

2.4 Black Channel Safety Communication

Black Channel is a safety communications approach in which the new safety functionality is built over existing protocol
without impact to existing safety applications. The Black Channel feature provides the transfer of Safety control data between
two Mark VIeS Safety control devices without using the standard UDH network, providing a safer, less congested network. A
matching pair of transmitter and receiver blocks, BLACK_TX and BLACK_RX, are configured for the two Mark VIeS Safety
control devices in the application. The data is passed through Ethernet (similar to UDH EGD), and the BLACK_TX and
BLACK_RX blocks run a data integrity check on each respective side of the Black Channel. For more information on these
blocks, refer to the Mark VIeS Safety Control Block Library (GEI-100691), the chapters Black Channel Transmitter (BLACK_
TX) , Black Channel Receiver (BLACK_RX), and Black Channel Example.
Transmitting Device
App
BLACK _TX
Block
Var 1
Var 2
Var 3
Var 4
Sequence
Number
Transmit
Connection
Block
ID
Data
Signature

2.5 Controller Setup and Download

After a controller and associated I/O modules have been added to the system, prepare the controller for use by configuring the
IP address and redundancy information using the ToolboxST application. For further instructions and procedures, refer to the
ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the sections Controller Setup and Build and
Download to Controller.
Controllers
EGD
EGD
Exchange
Packet
Produced
BlackChannel
Page
Example Black Channel Configuration
Public Information
EGD
EGD
EGD
Exchange
Consumed
BlackChannel
Page
Receive
Block
GEH-6855_Vol_II System Guide 37
Receiving Device
App
BLACK_TX
Block
Vardef
Var1
Var2
Var3
Var4
Sequence
Number
Connection
Data
ID
Exp
Connection
ID
Signature

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents