GE Mark VIeS System Manual page 203

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

The first time all channel 1–8 are disabled, the I/O pack will require a reboot. The first time all channel 9–16 are disabled, the
I/O pack will require a reboot.
The first time any channel 1–8 is enabled, the I/O pack will require a reboot. The first time any channel 9–16 is enabled, the I/O
Attention
pack will require a reboot.
Current Outputs
Current Outputs
OutputState
Description
State of the output
when offline
Choices
HoldLastValue
{defaults}
OutputValue
{PwrDownMode}
Scroll all the way to the right to find this value because the field does not appear directly right of the High_Value as expected.
If the I/O pack loses communication with the controller, OutputState determines how it drives the outputs as follows:
PwrDownMode: drive outputs to zero current
HoldLastVal: hold the last value received from the controller
Output_Value: go to the configured output value set by the Output_Value (units are Engineering Units, not mA)
Low_MA, Low_Value, High_MA, High_Value settings are used by the I/O pack firmware to define the linear relationship between customer-defined engineering units and
output mA. The I/O Point value will be in Engineering units, and the firmware will convert it to mA. Engineering units are specific to the field device being used.
YUAA Universal I/O Modules
Low_MA
Low_Value
Output low in mA
Low output value in
engineering units
{4}
{0}
Public Information
High_MA
High_Value
Output high in mA
High output in
engineering units
{20}
{100}
GEH-6855_Vol_II System Guide 203
Output_Value
This field is only
available if
OutputState =
OutputValue
{0}

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents