When the Redundancy OK floating signal contact opens, it indicates the loss of redundancy. Loss of redundancy may be a
result of the following issues:
The decoupled component is defective.
At least one input voltage is too low or does not exist.
If the load current is higher than the set threshold value of I
(indicated after 4 sec).
When the ACB OK floating signal contact opens, it indicates that the load current is not distributed symmetrically on both
parallel connected power supply units.

ABC OK Signal Output Operation

10.10.3.7 Power Supply Redundant Operation

Redundant power supplies are recommended for use in systems with especially high requirements for operational safety. With
redundant power supplies, if a fault occurs in the Primary circuit of the first power supply, the second device automatically
takes over supplying power, without interruption, and vice versa. For this purpose, the power supply units to be connected in
parallel are dimensioned so that the total current requirement of all consumers is completely covered by one power supply
unit. However, 100% redundancy makes external decoupling diodes (GE Part Number 342A3648PD40A48) necessary.
PDM Power Distribution Modules
, a single power supply unit can no longer sustain the load
N

Redundancy OK Signal Output Operation

Redundant Parallel Connection

Public Information
GEH-6855_Vol_II System Guide 417