Firmware Load Error - Incompatible FPGA Revision: Found [ ] Need [ ]
Possible Cause
During commissioning or maintenance:
Incompatible version of firmware downloaded
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
During normal operation:
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
Replace the I/O pack or module.
269
Note This alarm is obsolete.

Description EGD communication Initialization Failure

Possible Cause

Internal runtime error

Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
270
Note This alarm is obsolete.

Description EGD communication terminated

Possible Cause
Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.