8.2.1 YVIB Compatibility
The YVIB I/O pack contains an internal processor board. The following table lists the available versions of the YVIB.
I/O Pack
Processor
Board
†
YVIBS1B
BPPC
†
Internal to the I/O pack and are not replaceable.
‡
YVIBS1B supports an additional KeyPhasor* input, a CDM input, and other enhanced processing capabilities.
Attention
Attention
The YVIB I/O pack is compatible with the Vibration (TVBA) terminal board.
Terminal Board
TVBAS2B
Note Refer to the section
TVBA Compatibility
I/O pack redundancy refers to the number of I/O packs used in a signal path, as follows:
•
Simplex uses one I/O pack.
•
TMR uses three I/O packs.
YVIB Vibration Monitor Modules
YVIB Version Compatibility
Application
Compatible
Board
†
(Supported)
Firmware
BBAA
V05.01 and later Supported in
YVIBS1B cannot be mixed on a TMR module.
If upgrading to YVIBS1B with an existing YVIBS1A configuration, use the ToolboxST
application to correct the GAP12 configuration. Refer to the replacement procedure
To replace a YVIB I/O pack
After upgrading existing YVIBS1A applications to YVIBS1B, the user may need to
use the configurable low-pass filter to roll-off responses to match existing
peak-to-peak calculations. This is because the YVIBS1B has an increased input signal
bandwidth of 4500 Hz.
YVIB Terminal Board Compatibility
Description
Safety vibration terminal board with buffered outputs;
N28 function integrated into terminal board and YVIB
S-position is lined up vertically with R and T positions.
for additional information.
Public Information
ControlST
Enhanced
Versions
Signal Mode
Yes
V06.02 and later
in the section YVIB I/O Pack Replacement.
GEH-6855_Vol_II System Guide 229
Channels
Sensor
‡
Types
13
Refer to the table
YVIB Supported
Sensor Inputs.
I/O Pack Redundancy
Simplex
Dual
TMR
Yes
No
Yes