Description Channel [ ] Sensor type is not supported with this hardware
Possible Cause The selected sensor type (VIB_Type) is unsupported by this module. This is likely caused by installing a
replacement module without updating ToolboxST. This channel will default to Unused behavior.
Solution
Change the VIB_Type for the indicated channel to a value supported by all hardware forms being used. Review the
documentation to see which sensor types can be used for each hardware form.
Replace this module with a functionally compatible module.
88-95
Description Channel [ ] Wideband Filters do not support [ ]-pole filter attenuation. Falling back to [ ]-pole filter
attenuation.
Possible Cause The filter attenuation selection for Fltrhpattn and/or Fltrlpattn is not supported by this module. This is
likely caused by installing a replacement module without updating ToolboxST. This channel will run with the closest match it
can support, rather than disable the filter.
Solution
Change the Fltrhpattn and/or Fltrlpattn for the indicated channel to a value supported by all the hardware forms being
used. Review the documentation to see which attenuation values can be used for each hardware form.
Replace this module with a functionally compatible module.
192-221
Description Input Signal [ ] Voting Mismatch, Local=[ ], Voted=[ ]
Possible Cause
There is a voter disagreement between the R, S, and T I/O packs.
The I/O pack is not seated on the terminal board correctly.
The I/O pack has failed.
Solution
Adjust the parameter TMR_DiffLimt or correct the cause of the difference.
Re-seat the I/O pack to the terminal board.
Replace the I/O pack.
YVIB Vibration Monitor Modules