6.7.1 TRLYS#F Compatibility

The TRLYS1F and TRLYS2F terminal boards only supports TMR applications. Three TMR I/O packs plug into the JR1, JS1,
and JT1 37-pin D-type connectors on the terminal board.
Board Revision
TRLYS1F
TRLYS2F

6.7.2 TRLYS#F Installation

Connect the wires for the 12 solenoids directly to two I/O terminal blocks on the terminal board. Each block is held down
with two screws and has 24 terminals accepting up to #12 AWG wires. A shield termination strip attached to chassis ground is
located immediately to the left side of each terminal block. Alternatively, customer power may be wired to the terminal block.
The 28 V dc power for the terminal board relay coils and logic comes from the three I/O packs connected at JR1, JS1, and
JT1.
156
GEH-6855_Vol_II
Mark VIeS IS420YDOAS1B
Yes, all versions
Yes, all versions
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Safety Rated
Normally open (NO) contacts, IEC 61508
safety certified with Mark VIeS YDOA
Normally closed (NC) contacts, IEC 61508
safety certified with Mark VIeS YDOA