6.5.3.3 TMR

For TMR applications, relay control signals are fanned into TRLYS1B from the three I/O processors R, S, and T through
plugs JR1, JS1, and JT1. These signals are voted and the result controls the corresponding relay driver. Power for the relay
coils comes from all three I/O packs and is diode-shared.

TRLYS1B Circuits, TMR