501
Description Total memory consumption has exceeded [ ] percent
Possible Cause Memory usage is driven from three functions:
•
The online download procedure temporarily stores the previous and new application configuration in memory.
•
The footprint of the application configuration/code has been enlarged.
•
Memory usage can grow over time if there is a memory leak.
Solution
•
The alarm should return to normal state after download is complete.
•
Reduce the content of the application configuration/code.
•
To address a memory leak, reboot the device to reinitialize baseline memory use. Monitor for reoccurrence and contact
your GE representative.
502
Description Syspage inconsistency detected
Possible Cause Memory corruption
Solution Restart the controller to re-initialize QNX syspage.
503
Description Communications timeout with Remote System Log Server
Possible Cause
•
Remote Syslog server not in network
•
Remote Syslog server down
•
Incorrect Remote Syslog server IP address in system configuration
•
Network issue (cables/switch) connecting controller to Remote Syslog server
Solution
•
Verify that the Remote Syslog server is in operation.
•
Verify that the correct Remote Syslog server IP address in the system configuration.
•
Check the network connections.
Controllers
Public Information
GEH-6855_Vol_II System Guide 65