Incorrect Or Missing Acquisition Board On Hssl Link 2; Incorrect Or Missing Acquisition Board On Hssl Link 3; Acquisition Board Barcode Mismatch On Hssl Link 1; Acquisition Board Barcode Mismatch On Hssl Link 2 - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

446
Description

Incorrect or Missing Acquisition Board on HSSL link 2

Possible Cause
The acquisition card on High Speed Serial Link 2 is not connected or does not agree with the ToolboxST
configuration.
Solution
Verify that the correct acquisition card is connected to the specified HSSL connector on the UCSA.
Verify that the ToolboxST configuration for the appropriate HSSL connector matches the hardware.
447
Description

Incorrect or Missing Acquisition Board on HSSL link 3

Possible Cause
The acquisition card on High Speed Serial Link 3 is not connected or does not agree with the ToolboxST
configuration.
Solution
Verify that the correct acquisition card is connected to the specified HSSL connector on the UCSA.
Verify that the ToolboxST configuration for the appropriate HSSL connector matches the hardware.
448
Description

Acquisition Board barcode mismatch on HSSL link 1

Possible Cause
The barcode on the acquisition card connected to High Speed Serial Link 1 does not agree with those
provided in the ToolboxST application
Solution
Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
449
Description

Acquisition Board barcode mismatch on HSSL link 2

Possible Cause
The barcode on the acquisition card connected to High Speed Serial Link 2 does not agree with those
provided in the ToolboxST application
Solution
Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
450
Description
Acquisition Board barcode mismatch on HSSL link 3
Possible Cause
The barcode on the acquisition card connected to High Speed Serial Link 3 does not agree with those
provided in the ToolboxST application
Solution
Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
Common I/O Module Functionality
Public Information
GEH-6855_Vol_II System Guide 471