Configuration File Load Error - Invalid Header Size - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

368
Description

Configuration file load error - invalid header size

Possible Cause
During commissioning or maintenance:
Build error
Controller EGD revision code not supported
Incompatible version of I/O pack or module firmware was downloaded
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module
During normal operation: Replace the I/O pack or module.
369
Description Internal communication error - Exchange [ ] Export failed
Possible Cause
Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
370
Note This alarm is obsolete.
Description Internal EGD communication error - Exchange [ ] Import failed
Possible Cause Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.