4.3.1 Installation
Connect the input and output wires directly to two I/O terminal blocks mounted on the terminal board. Each block is held
down with two screws and has 24 terminals accepting up to #12 AWG wires. A shield terminal attachment point is located
adjacent to each terminal block.
TBAI can accommodate the following analog I/O types:
Analog input, two-wire transmitter
Analog input, three-wire transmitter
Analog input, four-wire transmitter
Analog input, externally powered transmitter
Analog input, voltage ±5 V, ±10 V dc
Analog input, current 4-20 mA
Analog output, 0-20 mA
YAIC Analog I/O Modules
Public Information
GEH-6855_Vol_II System Guide 107