Thermocouple Value Beyond Range Of Configured Tc Type; Rtd Voltage Out Of Range; Rtd Current Out Of Range - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

195-226
Description IOPoint [ ] - Thermocouple value beyond range of configured TC type ([ ] deg)
Possible Cause
Thermocouple mV input exceeded range of linearization (lookup) table for this TC type. Refer to documentation for
specified thermocouple ranges.
Thermocouple configured as wrong type
Stray voltage or noise caused the input to exceed its range.
Solution
Check the field wiring, including shields.
Check the thermocouple for an open circuit.
Verify that the thermocouple type matches the configuration.
Measure the incoming mV signal and verify that it is within the specified thermocouple range.
2400-2431
Description IOPoint [ ] - RTD voltage out of range ([ ] mV)
Possible Cause
There is a break in the RTD wiring/cabling or high impedance is blocking the signal.
The sensor impedance is too high.
The RTD device has failed.
Solution
Check the field wiring for an open circuit or high impedance.
Verify that the connections to the terminal board are correct.
Check the RTD for proper operation and sensor type.
Replace the I/O pack.
2432-2463
Description IOPoint [ ] - RTD current out of range ([ ] mA)
Possible Cause
There is a break in the RTD wiring/cabling open or high impedance is blocking the signal.
There is a break in the connections to the terminal board.
The current source on the I/O pack has failed.
The measurement device has failed.
Solution
Check the field wiring for an open circuit or high impedance.
Verify that the connections to the terminal board are correct.
Replace the I/O pack.
220
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II