5.1.3 Specifications
Item
Number of relay channels
Input isolation in pack
Input filter ac voltage rejection
Frame rate
Fault detection
Size
Technology
Ambient rating for enclosure design
Note For further details, refer to the Mark VIeS Functional Safety Contact Input Module Summary Sheet (GEI-100862).
5.1.4 Diagnostics
The I/O pack performs the following self-diagnostic tests:
•
A power-up self-test that includes checks of RAM, flash memory, Ethernet ports, and processor board hardware
•
Continuous monitoring of the internal power supplies for correct operation
•
A check of the electronic ID information from the terminal board, acquisition board, and processor board to confirm that
the hardware set matches, followed by a check that the application code loaded from flash memory is correct for the
hardware set
•
Monitoring for loss of contact input excitation voltage on the terminal board
•
It detects a non-responding contact input during the diagnostic test. In this test, the threshold is pulsed high and low and
the response of the opto-couplers is checked.
Details of the individual diagnostics are available in the ToolboxST application. The diagnostic signals can be individually
latched, and then reset with the RSTDIAG signal if they go healthy.
5.1.4.1 YDIA Status LEDs
LED
Yellow
Note For more information, refer to the section
118
GEH-6855_Vol_II
YDIA Specification
24 dry contact voltage input channels
Optical isolation to 1500 V on all inputs
Hardware filter, 4 ms
60 V rms, 50/60 Hz at 125 V dc excitation
Configured frame rate of the controller determines I/O scan rate for control
Loss of contact input excitation voltage
Non-responding contact input in test mode
Incorrect terminal board
8.26 high x 4.19 wide x 12.1 deep cm (3.25 x 1.65 x 4.78 in)
Surface-mount
-40 to 70°C (-40 to 158 °F)
Discrete Input LEDs
Label
Description
Input #
Provided for each of the 24 inputs to indicate when they are energized
Processor
LEDs.
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information