6.2 YDOA Configuration

6.2.1 Inputs
Description
Parameter
ContactInput
Enables Relay#Fdbk
Inverts Relay#Fdbk signal and Relay#ContactFdbk signal (if available)
Do not rely on the SignalInvert property of digital inputs to invert the value.
SignalInvert
Implement this operation in the application code with the input connected to a
NOT block.
Record RelayFdbk transitions in sequence of events
SeqOfEvents
Not available with TRLYS1D.
DiagVoteEnab
Enable voting disagreement diagnostic
6.2.2 Outputs
Description
Parameter
RelayOutput
Enable relay output
Inversion makes relay closed if signal is false
Do not rely on the SignalInvert property of digital inputs to invert the value.
SignalInvert
Implement this operation in the application code with the input connected to a
NOT block.
SeqOfEvents
Record relay command transitions in sequence of events
FuseDiag
Enable fuse diagnostic (if available)
Output_State
Select the state of the relay condition based on I/O pack going offline with controller
Pre-determined value for the outputs (only displayed if Output_State is set to
Output_Value
Output_Value)
6.2.3 Variables
Description
Name
L3DIAG_YDOA_x
I/O diagnostic indication, where x = R, S, or T
LINK_OK_YDOA_x
I/O link okay indication, where x = R, S, or T
ATTN_YDOA_x
I/O Attention Indication, where x = R, S, or T
IOPackTmpr_x
I/O pack temperature, where x = R, S, or T
Description
Name
Relay#
Relay# output command
Relay#Fdbk
Relay# Driver Status (set of 12 relays)
Relay#ContactFdbk
Relay# Contact Status (set of 12 relays), available for SRLY only
Fuse voltage (if available)
Fuse#Fdbk
Solenoid# Resistance Sense (set of 6 relays), True means resistance within the
Solenoid#Status
range, False means resistance out of the range, available for TRLYS1D only
YDOA Discrete Output Modules
Public Information
Select Option or Enter
Value
Unused, Used
Normal, Invert
Disable, Enable
Disable, Enable
Select Option or Enter
Value
Used, Unused
Normal, Invert
Disable, Enable
Enable, Disable
PwrDownMode,
HoldLastValue, Output_
Value
Off, On
Type
Direction
Input
BOOL
Input
BIT
Input
BIT
Input
REAL
Type
Direction
Output
BIT
Input
BIT
Input
BIT
Input
BIT
Input
BIT