Description Application Runtime Error - [ ] Frame skips occurred
Possible Cause There is an overloaded processor or a processor malfunction. Frame number skips were detected. The
frame number should incrementally increase during Controlling state.
Solution
For a controller, do the following:
Reduce the application or increase the EGD period to reduce the processor load.
Upgrade the controller to one with a faster processor.
Replace the controller.
For an I/O module, do the following:
From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module.
Replace the I/O module.
279
Description Could not determine platform type from hardware
Possible Cause
During commissioning/maintenance: Incorrect firmware version or hardware malfunction (firmware could not recognize
host hardware type)
During normal operation: Hardware failure
Solution
Verify that all connectors are aligned properly and fully seated.
Check the firmware version for compatibility with platform. If correct, replace the controller.