280
Description Platform hardware does not match configuration
Possible Cause
•
During commissioning/maintenance: Platform type identified in the application configuration does not match actual
hardware
•
During normal operation: Hardware failure
Solution
Fix the platform type in the ToolboxST application. From the General tab, select General Properties and Platform.
•
•
Rebuild and download the application.
•
If problem persists, replace the controller.
282
Description Firmware Load Error - application independent processes failed to initialize
Possible Cause Runtime malfunction. An application-independent firmware process could not be started successfully.
Solution
•
Reload firmware and application and restart.
•
If controller is a UCSA, try formatting and reloading the flash memory.
•
If I/O pack has diagnostic: try to re-download the base load.
•
Replace the controller or I/O module.
283
Description Firmware error - Internal process crashed
Possible Cause Runtime or hardware malfunction (runtime process failed).
Solution
•
Reload firmware and application and restart.
•
If controller is a UCSA, try formatting and reloading the flash memory.
•
If this does not work, replace the controller.
46
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information