5.2 Configuration

5.2.1 Parameters
Parameter
ContactInput
SignalInvert
SeqOfEvents
DiagVoteEnab
Signal Filter
5.2.2 Inputs
Input
Contact01
Contact24
5.2.3 Variables
Note The following variable names are displayed differently depending on redundancy of I/O pack (R, S, or T).
Variable
Description
L3DIAG_YDIA_x
I/O diagnostic indication, where x is R, S, or T
LINK_OK_YDIA_x
I/O link okay indication, where x is R, S, or T
ATTN_YDIA_x
I/O attention indication, where x is R, S, or T
IOPackTmpr_x
I/O pack temperature, where x is R, S, or T
PS18V_YDIA_x
I/O 18 V power supply indication, where x is R, S, or
T
PS28V_YDIA_x
I/O 28 V power supply indication, where x is R, S, or
T
YDIA Discrete Input Modules
Description
Mark a specific contact input as Used or Unused.
Inversion makes signal true if contact is open
Record contact transitions in sequence of events
Enable voting disagreement diagnostic
Contact input filter in milliseconds
Direction
Input
Input
Public Information
Choices
Used, Unused
Normal, Invert
Enable, Disable
Enable, Disable
Zero, Ten, Twenty, Fifty, Hundred
Type
BOOL
BOOL
Direction
Type
BOOL
BOOL
BOOL
REAL
Input
BOOL
BOOL
GEH-6855_Vol_II System Guide 119