Disconnect / Re-Connect Addressable Zone Interface Input (H8/S3) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

27.3
Disconnect / Re-connect addressable zone interface input
(H8/S3)
To avoid damage on the units and FT128 during physical connection / disconnection of
units, it is highly recommended to have the zone interface input disconnected (disabled),
i.e. voltage free (dead).
Disconnected addressable zone interface input is indicated by LED "Disablements" and is
listed in menu H4/U1.
Action
"Access"
Scroll to menu H8.
"A"
Scroll to menu S3
"A"
Depending on if "0" or
"1" is chosen, one of
the following will be
shown:
E.g. "0"
"001"
"A"
"A"
"Return"
"Return"
"Return"
Text in display
Maintenance
Disconnect / Re-connect COM loop
Disconnect / Re-connect addressable zone
interface input
Disconnect (=0) or Re-connect (=1) addr.
zone interface input? 1
Disconnect addressable zone interface
input, technical address: 000
Re-connect addressable zone interface
input, technical address: 000
Input technical address 001 disconnected
Disconnect addressable zone interface
input, technical address: 000
Disconnect (=0) or Re-connect (=1) addr. zone interface
input? 1
Disconnect / Re-connect addressable zone interface
input
Maintenance
ACCEPT? H8
ACCEPT? S1
ACCEPT? S3
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? S3
ACCEPT? H8
125
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as
shown in page 35.
Press "0" or "1" and
press "A" to accept.
Write the COM loop
address (001-255).
Press "A" to accept.
Do more disconnections
or press "Return".
Write "0" or "1" and
press "A" to accept or
press "Return" menu S3.
Scroll or press "Return"
to H8.
Scroll or press "Return".