Restore Weekly Average To Default (H8/S5) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

27.5

Restore Weekly Average to Default (H8/S5)

Valid only for 430x, 4400 and 4401 sensors in NORMAL mode.
If a sensor (analogue smoke detector) is replaced without having generated SERVICE
signal, its week average sensor value has to be cleared and set to the default value (i.e.
"1" = 0.1 %/m), otherwise the new / clean sensor will inherit the old sensor's value.
The week average sensor value has to be restored for each replaced sensor individually.
First replace the sensor then restore the week average sensor value as soon as possible.
Note: First replace the sensor and then clear the week average value as soon as
possible. Authorised service personnel only, must do this. Used incorrectly it can cause
nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated within one hour, then
each week.
Action
Text in display
"Access"
Scroll to menu H8.
Maintenance
Disconnect / Re-connect COM loop
"A"
Scroll to menu S5.
Restore weekly average to default
"A"
Enter zone-address to restore: 00-00
E.g. "01-01"
Sensor 01-01 (tech addr 001) is restored
"A"
to default average
Enter zone-address to restore: 00-00
"A"
"Return"
Restore weekly average to default
"Return"
Maintenance
ACCEPT? H8
ACCEPT? S1
ACCEPT? S5
ACCEPT?
ACCEPT?
ACCEPT? S5
ACCEPT? H8
127
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as
shown in page 35.
Write the zone-address
and press "A" to accept.
If more sensors shall be
restored, continue like
above. If not, press
"Return" to menu S5.
Scroll or press "Return"
to menu H8.
Scroll or press "Return".