User Level 2B - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

6.3.5

User Level 2B

After the door has been opened using 003 key (LED "Door open" is lit), you have access
to level 1 and after log on as "Building officer" (level 2B), the following menus will be
accessible:
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calendar and clock.
H4 Present system status
H6 Acknowledge FAULTS.
H7 Perform ZONE TEST (Test mode).
H9 Interlocking outputs and inputs
H10 Change password (In this case for "Building officer")
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Disable all control, ventilation, extinguishing or interlocking outputs
B5 Re-enable zone
B6 Re-enable zone / address
B7 Re-enable output
B8 Re-enable all control, ventilation, extinguishing or interlocking outputs
B9 Disable / Re-enable alarm devices
B10 Disable / Re-enable outputs for routing equipment
B11 Disable / Re-enable alert annunciation function
U1 Disablement
U2 Disablement by time channel.
U3 Sensor values.
U4 Sensors activating SERVICE signal
U5 Technical warning
U6 Event log
U7 Version and alarm counter
C1 Activated interlocking outputs/inputs
C2 Activate interlocking output
C3 Reset interlocking output
C4 Disable interlocking output
C5 Re-enable interlocking output
38
Operation Manual
FT128 Rev 2.4