12
"Disable" Button
When the push button "Disable" (P5) is pressed whilst there is an active alarm, all outputs
configured for either the device(s) or zone(s) in alarm, will be disabled. This is indicated by
the disablement LED L8.
The "Disable" push button (P5) is provided in the fire brigade section on the front display
to enable the fire brigade personnel to disable (isolate) an active alarm such as a zone of
addressable sensors, conventional zone or individual addressable device.
A single operation of the "Disable" button (P5) whilst there is an active alarm will initiate
the following:
Disablement of all zones in alarm and/or addressable devices in alarm.
Illuminate the "General Disablement" LED L10.
Disablement of all the outputs configured for zone(s) or device(s) in alarm.
The output indicators activated as a result of an alarm will not clear automatically after
disablement. A subsequent reset operation is required to restore the FDCIE to the normal
condition.
Note: The "Disable" button will not function unless the "Silence Alarm Devices" button
has been activated first as required by AS4428.3:2010
33
This function is not required in NZ convention.
33
.