Re-Enable All Control, Ventilation, Extinguishing, Or Interlocking Outputs (H2/B8) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

21.8
Re-Enable All Control, Ventilation, Extinguishing, Or
Interlocking Outputs (H2/B8)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8) will be extinguished,
if there are no other disablements.
If there is nothing to re-enable,
Action
Text in display
"Access"
Scroll to menu H2.
Disable or re-enable
"A"
Disable zone
Scroll to menu B8.
Re-enable all control, ventil, exting
or interlocking outputs
"A"
Re-enable type:0 0=Control 1=Ventilation
2=Exting 3=Interlocking
Or, e.g. if only type 1 is disabled:
Re-enable type:0
Press 1
"A"
"Return"
Re-enable all control, ventil, exting
or interlocking outputs
"Return"
Disable or re-enable
--- List is empty ---
ACCEPT? H2
ACCEPT? B1
ACCEPT? B8
ACCEPT?
1=Ventilation
ACCEPT?
--- List is empty ---
ACCEPT? B8
ACCEPT? H2
95
Operation Manual
FT128 Rev 2.4
will be shown.
Comments
Log on to FT128 as shown
in page 35.
Only disabled type(s) will
be shown. Press:
"0"=control output
"1"=extinguishing output
"2"=ventilation output
"3"=interlocking output.
Press "A" to accept.
All types are re-enabled.
Scroll or press "Return" to
menu H2.
Scroll or press "Return".

Advertisement