Calibration Of Supervised Outputs (H5/A1) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

24.1

Calibration of Supervised Outputs (H5/A1)

Supervised (monitored) outputs
The voltage outputs (S0-S1) in the control unit
The voltage outputs (VO0-VO1) in the COM loop output unit 3364.
The voltage outputs (Output 0-Output 1) on the I/O expansion board 4583
When all alarm devices (OWS, sounders, etc.) are connected, including required End-Of-
Line devices
Function: If the actual value differs from the calibrated value ± a small tolerance or if the
calibrated value is outside the calibration range
Action
Text in display
"Access"
Scroll to menu H5
Service
"A"
Calibration of supervised outputs
To calibrate supervised outputs press
"A"
ACCEPT
Calibration in progress
"A"
Please wait......
"A"
Calibration is completed
Calibration of supervised outputs
"A"
Service
Note: During the calibration, all outputs will automatically be low, i.e. a normally high
output will be low during the calibration for a few seconds.
Note: After the calibration it is recommended to do a "Safe shutdown of control unit" (see
menu H8/S4). This will save the SSW data (e.g. the calibration values) in a Flash ROM
(see page 82).
64
Supervised (monitored) outputs can be set to be not supervised via EBLWin.
65
FT128 outputs (S0-S1) requires one EOL resistor (33K) in the last unit or one resistor (33K) in up to five units, 3364 outputs
(VO0-VO1) requires one EOL capacitor (470 nF) in the last unit or one capacitor (470 nF) in up to five units.
66
4K7 – 50K and 470 – 5x470 nF respectively.
64
:
65
and when the SSD download is ready, a calibration has to be done.
110
66
, a fault will be generated.
Comments
Log on to FT128 as shown
in page 35.
ACCEPT? H5
ACCEPT? A1
ACCEPT?
Scroll or press "Return" to
ACCEPT? A1
H5.
Scroll or press "Return"
ACCEPT? H5
Operation Manual
FT128 Rev 2.4