Test of Alarm Devices (H8/S6)

The programmable outputs
sub menu (S6), which enables the service technician to test the alarm devices without too
much disturbance on site.
The test cannot be started if fire alarm is already activated in FT128
When the test starts, the alarm devices will sound for approx. 1 seconds, be silent for
approx. 29 seconds, sound for approx. 1 seconds and so on.
Note: Disabled (and silenced) alarm devices will also be tested. The test will continue
for one hour if not stopped via this menu (H8/S6) or if a fire alarm is activated in the
system.
Action
Text in display
"Access"
Scroll to menu H8.
Maintenance
"A"
Acknowledge SERVICE signal
Scroll to menu S6.
Test of alarm devices
"A"
Test of alarm devices?
"A"
Test of alarm devices in progress.
End test?
"A"
Test of alarm devices?
"Return"
Test of alarm devices
"Return"
Maintenance
70
Including Addressable siren 3377 / 4477, Addressable sounder base 3379, wireless detector 4611, and all visual alarm devices
4480, 4481, 4482, 4487.
71
The output activation will be steady (continuous). For the alarm devices 3377 / 4477 and 3379, 4611, 4480, 4481, 4482 and
4487, the tone with the highest priority level (and type "alarm device") will be automatically selected.
70
of type "Alarm device" can be collectively activated via this
ACCEPT? H8
ACCEPT? S1
ACCEPT? S6
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? S6
ACCEPT? H8
128
Operation Manual
FT128 Rev 2.4
71
Comments
Log on to FT128 as
shown in page 35.
Press "A" to start the
test.
The test will now
continue until stopped
via this menu (S6) or
automatically after one
hour or if a fire alarm is
activated.
Press "A" to stop the
test.
Scroll or press "Return"
to return to menu H8.
Scroll or press "Return"