28.4

Disable Interlocking Output (H9/C4)

Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (and
collectively via menu H2/B3). The "Interlocking Combination" (Area / Point) is to be entered
to disable the output.
Up to 100 interlocking outputs can be disabled in the system.
Disabled interlocking outputs are listed in menu H4/U1.
The LED "Disablements" is also indicating one or more disabled interlocking outputs.
Re-enable is performed via menu H9/C5.
Action
"Access"
Scroll to menu H9.
Interlocking outputs and inputs
"A"
Activated interlocking outputs/inputs
Scroll to menu C4.
Disable interlocking output
Disable interlocking output
"A"
area 00
e.g.: "01", "01"
Disable interlocking output
area 01
"A"
"A"
interlocking output 01 – 01 disabled
Disable interlocking output
"A"
Scroll to menu H9.
Interlocking outputs and inputs
Text in display
point 00
point 01
137
Log on to FT128 as shown in
page 35.
ACCEPT? H9
ACCEPT? C1
ACCEPT? C4
ACCEPT?
Press "A" to accept and/or
ACCEPT?
"Return" to menu C4.
Scroll or press "Return" to
ACCEPT? C4
menu H9.
Scroll or press "Return"
ACCEPT? H9