21.2

Disable Zone / Address (H2/B2)

Up to 100 addressable alarm points (also addressable manual call points), connected to
the COM loop, can be individually disabled.
Disabled alarm points (zone – address) are listed in menu H4/U1.
Disabled alarm points (zone – address) can be automatically re-enabled or via menu
H2/B6.
Note: The sensor values for disabled analogue smoke detectors in NORMAL mode will
not be used for calculation of the week average sensor value, i.e. only the values saved
before and after the disablement will be used for this calculation.
Action
"Access"
Disable or re-enable
Scroll to menu H2.
Disable zone
"A"
Disable zone / address
Scroll to menu B2.
Disable zone: 0 0 Address: 00
"A"
Write zone number
Disable zone: 01 Address: 01
and address
e.g. 01 - 01
Automatic re-enabling: 0 (0=No,1=Yes)
"A"
(Default is current time + 3 hours)
"A"
Zone 01 address 01 is disabled
Disable zone: 0 0 Address: 00
"A"
Disable zone-address
"Return"
Disable or re-enable
"Return"
Text in display
Time: HH:MM
ACCEPT? H2
ACCEPT? B1
ACCEPT? B2
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? B2
ACCEPT? H2
89
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as shown in
page 35.
Press "A" to accept.
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours).
Press "A" to accept. LED
"Disablements" (L8) will
light up.
If more disablements
required, continue as
above otherwise, press
"Return" to menu B2.
Scroll or press "Return" to
menu H2.
Scroll or press "Return"