Disable / Re-Enable Alarm Devices (H2/B9)

Disabled alarm devices are listed in menu H4/U1.
Outputs for alarm devices can be collectively disabled and re-enabled via this menu.
Disabled output will stay disabled, until re-enabled again via this menu.
When all outputs type Alarm devices have been disabled, the LEDs "Disablements" (L8)
and "Fault / Disablements Alarm devices" (L13) will be illuminated.
When all outputs type Alarm devices have been re-enabled, the LED "Fault /
Disablements Alarm devices" (L13) will be extinguished.
Note: This function for alarm devices is not the same as for push button "Silence alarm
devices" (P3) – unless the option Button "Silence alarm devices" disables alarm devices,
is selected in EBLwin System properties, see chapter "Silence Alarm devices", page 42.
This menu has higher priority than the push button "Silence alarm devices".
Action
Text in display
"Access"
Scroll to menu H2.
Disable or re-enable
"A"
Disable zone
Scroll to menu B9
Disable / re-enable alarm devices
"A"
Alarm devices in normal condition
Press ACCEPT to disable
"A"
Alarm devices disabled
Press ACCEPT to re-enable
Disable or re-enable outputs for
"Return"
routing equipment
Disable or re-enable
"Return"
ACCEPT? H2
ACCEPT? B1
ACCEPT? B9
ACCEPT? B9
ACCEPT? H2
96
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as shown
in page 35.
Depending on the actual
status one of the texts will
be shown.
Scroll or press "Return" to
return to H2.