Door Open

A standard 003 key is used to open the FT128 door and get access to the front membrane
and other optional modules e.g. OWS, zone disable, AS1668 fan control, etc., see also
chapter "User ", page 34.
Door open may be programmed via EBLWin to disable any external strobe or
sounder/strobe combination located at the designated building entry point.
Door open in FT128 is indicated by LED "Door open" (L10) in FT128.
13.1

Disable Routing Equipment with Door Switch

Note: Do not use the door open function to disable (isolate) the routing equipment. This
option cannot be selected in Both Australia and New Zealand, it is a violation to
AS4428.3.
In EBLWin the following options are available to program:
None: The output(s) for routing equipment (Fire Brigade and Fault TX) will not be disabled
by any open door (default).
Any Control Unit Door: Door open in FT128 will disable the output(s) for routing
equipment (Fire Brigade and Fault TX).
Any Door: Door open in FT128 and/or Ext. Fire Brigade Panel will disable the output(s)
for routing equipment (Fire Brigade and Fault TX).
Disabled routing equipment outputs are indicated by the LED "Disablements" (L8) and
"Fault / Disablements Fire Brigade TX" (L15) and listed in menu H4/U1.
The following is shown in the display:
A l l o u t p u t s t o f i r e a l a r m r o u t i n g e q u i p m e n t
d i s a b l e d b y d o o r s w i t c h
13.2

Silence Buzzer by Door Switch

In EBLWin the following can be programmed:
The buzzer will be turned off as long as the FT128 door is open.
48