Disable Zone (H2/B1) - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

21.1

Disable Zone (H2/B1)

When a whole zone is disabled, all alarm points within the zone are disabled.
Alarm points can be individually disabled.
Disabled zones can be automatically re-enabled or re-enabled via menu H2/B5.
Action
"Access"
Disable or re-enable
Scroll to menu H2.
Disable zone
"A"
Disable zone: 0 0
"A"
Disable zone: 01
Write zone number
e.g. 01
Automatic re-enabling: 0 (0=No, 1=Yes)
Time: HH:MM
"A"
(Default is current time + 3 hours)
Zone 01 is disabled
"A"
Disable zone: 0 0
"A"
Disable zone
"Return"
Disable or re-enable
"Return"
Text in display
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? B1
ACCEPT? H2
88
Operation Manual
FT128 Rev 2.4
Comments
Log on to FT128 as shown
in page 35.
Press "A" to accept.
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours). Press "A" to accept.
LED "Disablements" (L8)
will light up.
If more disablements
required, continue as above
otherwise, press "Return" to
menu B1.
Scroll or press "Return" to
menu H2
Scroll or press "Return"

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firetracker ft128 fdcie

Table of Contents