Alternative a)
"Reset"
Alternative b)
"Reset"
Note: Multiple reset is default.
72
Alarm reset is selected via EBLWin, "Control Unit Properties", tab "Advanced".
This manually activated fire alarm will be presented as "Test mode alarm" in the
control unit display and all external FBP displays and indicated by the LEDs "Fire"
and "Fire brigade tx".
The LEDs "Alarms queued" are indicating that more than one alarm point is in
alarm. Press the button "Alarms queued" to see the other alarm. Press "Reset" to
reset the alarm(s).
What happens when you press "Reset" is dependent on:
1. if you still are in menu H8/S8 and single encapsulated reset is used
2. if you still are in menu H8/S8 and multiple reset is used or if you have left
the menu system (by pressing "Return" two times or automatically after
10 minutes).
Activate zone/address in alarm mode
Maintenance
(Blank)
72
ACCEPT? S8
ACCEPT? H8
131
Operation Manual
FT128 Rev 2.4
Scroll or press "Return"
to menu H8.
Scroll or press "Return".