15.9

Local Alarm Acknowledgement (LAA) Reset

The indication in the Control Unit display, during the Acknowledgement Period (10-120
sec.) and the Investigation Period (1-9 min.) respectively, will automatically clear when:
The AA process ends because no detector in the LAA zone is over the fire alarm
level.
The AA process ends up in a fire alarm, which has higher priority.
15.10

Quiet Alarm Reset

Quiet alarms are non-latching, i.e. they will be automatically reset when the alarm point /
zone is no longer above alarm level. Outputs activated by quiet alarm will be de-activated
(In some cases after a programmable delay time).