3.4.1

LED Indicators and Push Button

LED's and push buttons are contained on the front panel display and are described in the
tables below. See also Figure 3 above, for the LEDs and push buttons.
3.4.1.1

Fire Brigade Panel Display and Control

Table 4 Fire Brigade Panel LED Indicators and Push Buttons

No.
L1
Fire
L2
Alarms queued
L3
Extinguishing
L4
Ventilation
L5
Fire Brigade TX
L6
Operation
P1
Alarms queued
P2
Silence buzzer
Silence Alarm
P3
devices
P4
Reset
P5
Disable
9
In the New Zealand convention also "Acknowledged alarm" (ACK).
10
L3, L4 and L5 can as an alternative be programmed to indicate when a programmable input is activated, i.e. input trigger
condition "Extinguishing system released", "Activated fire ventilation" and "Activated routing equipment" respectively (e.g. L5
can be turned on when a programmable input is activated by an activated routing equipment output). L5 is turned on until all
fire alarms are reset.
11
Via EBLWin can be set if the alarm devices are to be continuously off / disabled or re-sound for a new alarm.
Label
Colour
5 x Red
2 x Red
Red
Yellow
Red
Green
BLACK
Yellow
Red
Green
Yellow
Indicating / Action
Fire alarm, Quiet alarm, etc. See Alarm Types
9
page 49
More than one unit / zone has generated fire
alarm. Use push button "Alarms queued" (P1) to
scroll amongst the alarm points (zone-address).
Output(s) for extinguishing equipment
(or a programmable input type "Extinguishing" is
activated).
Output(s) for fire/smoke ventilation equipment
activated
(or
a
programmable
"Ventilation" is activated.)
Output for "Fire alarm" for Fire Brigade TX (routing
equipment) activated. Or a programmable input(s)
type "Activated routing equipment" is activated. Or
test of routing equipment in progress (see menu
H1).
Power on, i.e. the FT128 power supply (switch
mode
power
supply
connected and working properly.
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
Used to silence the buzzer in FT128
Used to silence devices configured as "Alarm
devices" such as sounders or OWS (i.e. to "reset"
outputs for alarm devices).
Used to reset the fire alarm(s), has to be pressed
for > 0.5 Secs
Used to disable active alarm(s), all outputs of the
device or zone in alarm will be disabled.
17
Operation Manual
FT128 Rev 2.4
10
activated
10
input
type
and/or
batteries)
are
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firetracker ft128 fdcie