Restart

A restart may delete some data in FT128. Below follows an explanation of the different
data, abbreviations and a table describing the different restart alternatives and how the
data respectively is affected (cold or warm restart).
FF
D
FFD
SSW
WASV
SSD
S/W
The date & time and alarm counter value is stored in the memory of the real time clock,
i.e. the value will be retained also after the FT128 powered down.
Note: After any restart, a new week average sensor value will be calculated within 2
minutes, for all the Analogue smoke detectors
will be calculated each week.
19.1

Safe Shut Down

Safe shut down of control unit via menu H8/S7 will save the SSW data in a Flash ROM in
FT128. Before the first "Safe shut down" of the control unit, this memory is empty. After
each "Safe shut down" the latest SSW data is saved. (Safe shut down will not save the
week average sensor values)
When FT128 is powered up, a restart takes place and the RAM (working memory) will read
the SSW data saved in the Flash ROM.
19.2

Restart Table

Table 15 below describes the different reset alternatives and how the data is affected.

Table 15 Data affected by restart

Power down
again. ("Cold restart")
Via menu H8/S4 Safe shut down of
control unit. ("Cold restart")
Automatically after download of site
specific data (SSD) via a PC & EBLWin.
("Warm restart")
Automatically after download of
S/W via a PC & EBLWin. ("Cold restart")
Automatically due to external
disturbance. ("Cold restart")
57
During these 2 minutes, all fire alarms from analogue smoke detectors will be suppressed.
58
Both the power supply (mains) and the batteries are disconnected.
= Fire alarms and Faults.
= Disablements
= Fire alarms, Faults and Disablements.
= Sensor min. / max. values and performance factor, password, supervised
output calibration values and event log.
= Week Average Sensor Values
= Site Specific Data, i.e. all the installation programming created and
downloaded via EBLWin.
= Software, i.e. the EBL128 system program.
Action
58
and then power up
57
. Thereafter a new average sensor value
Data -
Data - not
Deleted
SSW
SSD,
FFD, WASV
S/W
SSD,
FFD, WASV
S/W, SSW
FF, WASV, D
SSD,
S/W, SSW
FFD, WASV
SSD,
S/W, SSW
SSD,
FFD, WASV
S/W, SSW
82
Operation Manual
FT128 Rev 2.4
Restart
Deleted
code
00
00 alt. 03
25
03
01, 02 alt.
04-20

Advertisement