Nz Fire Brigade (Led) Mimic Board; Figure 5 Zone Control & Indication Display; Table 9 Zone Control Leds And Buttons - Panasonic Firetracker FT128 Operation Manual

Table of Contents

Advertisement

refer to the Technical / Programming manual and to drawing no. F665 in Figure 27 page
145

Table 9 Zone control LEDs and Buttons

LED indicator & buttons
AL
DS
FT
Disable
LED Test
4.4

NZ Fire Brigade (LED) Mimic Board

The generic feature in EBLWin software supports the mimic applications of the I/O matrix
board 4582. This feature is used in the New Zealand fire brigade mimic panels or the
standard index panels.
Each NZ mimic board provides 12 LED indicators and screw terminals for 4 inputs
(switches). The first 3 LEDs used for Normal (green), Defect (yellow) and common alarm
(red). The remainder 9 LEDs (red) used to indicate separate zone alarm indications or
sprinkler flow switch indication. Two of the four inputs are used to interface the Bulgin keys
to the FDCIE. Additional mimic boards provide 12 red LED indicators for each board.
Up to 4 mimic boards can be interfaced to each I/O matrix board 4582 to provide
indications for up to 48 LED's, up to two I/O matrix boards can be used in the NZ mimic
applications, if no zone control modules used. Total number of LED indicators that FT128
can provide is 96 indicators.
The new design of NZ mimic boards provides an option to allow for remote mounting of
LED's via screw terminals. This can be used (if required) to mount individual LEDs on a
building layout.
Figure 6 below shows an example of a mimic display used in conjunction with FT128 in
New Zealand Steel.
ZONE CONTROL
AL
Disable
DS
Disable
FT
AL
Disable
DS
Disable
FT
AL
Disable
Disable
DS
FT
Figure 5 Zone Control & indication Display
Indicating
Illuminates when an alarm from a conventional zone
Alarm – Red
or an addressable device or group of addressable
1-12
devices designated as a zone enters an alarm state.
Illuminates when a zone is disabled either by the
Disable-Yellow
disable switch on the zone control card or where the
1-12
zone is disabled via menu H2/B1
Illuminates when either a short circuit or open circuit
Fault – Yellow
fault on conventional zone or any fault that prevents
1-12
an addressable alarm point in a designated zone to
operate properly.
Pressing the disable switch will disable the selected
Button
zone. Pressing the switch a second time will re-
1-12
enable the zone. Functions same as menu H2/B1.
Is selectable to be activated either from the FDCIE or
at the Zone Control Module itself, this feature can be
Button
utilised when the module is mounted externally via
the COM loop.
23
AL
AL
DS
Disable
DS
Disable
FT
FT
AL
AL
DS
Disable
DS
Disable
FT
FT
AL
AL
Disable
Disable
DS
DS
FT
FT
LED
Test
Operation Manual
FT128 Rev 2.4
AL
DS
FT
AL
DS
FT
AL
DS
FT

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firetracker ft128 fdcie

Table of Contents